How to choose the reactance rate of series reactor?

How to choose the reactance rate of series reactor?

  • Categories:Industry news
  • Author:
  • Origin:
  • Time of issue:2021-12-31
  • Views:0

(Summary description)(1) The background harmonic at the connection point of the capacitor device is 3rd (when the background harmonic at the connection to the power grid is 3rd and above, it is generally 12%; 4.5% to 6% and 12% can also be used. reactance rate.)

How to choose the reactance rate of series reactor?

(Summary description)(1) The background harmonic at the connection point of the capacitor device is 3rd (when the background harmonic at the connection to the power grid is 3rd and above, it is generally 12%; 4.5% to 6% and 12% can also be used. reactance rate.)

  • Categories:Industry news
  • Author:
  • Origin:
  • Time of issue:2021-12-31
  • Views:0
Information
(1) The background harmonic at the connection point of the capacitor device is 3rd (when the background harmonic at the connection to the power grid is 3rd and above, it is generally 12%; 4.5% to 6% and 12% can also be used. reactance rate.)
1) The 3rd harmonic content is small, and a series reactor of 0.1% to 1% can be selected, but it should be checked whether the 3rd harmonic amplification exceeds or is close to the national standard limit after the capacitor device is put into use, and there is a certain margin.
2) The 3rd harmonic content is relatively large, which has exceeded or is close to the national standard limit. Choose a series reactor of 12% or 12% and 4.5% to 6%.
(2) The background harmonics at the access point of the capacitor device are the 3rd and 5th times
1) The 3rd harmonic content is very small, and the 5th harmonic content is relatively large (including exceeding or close to the national standard limit), choose a series reactor of 4.5% to 6%, and avoid using a series reactor of 0.1% to 1% .
2) The 3rd harmonic content is slightly larger, and the 5th harmonic content is smaller. Choose a series reactor of 0.1% to 1%, but it should be checked whether the 3rd harmonic amplification exceeds or is close to the national standard limit after the capacitor device is put into operation, and There is a certain margin.
3) The 3rd harmonic content is relatively large, which has exceeded or is close to the national standard limit. Choose 12% or 12% and 4.5% to 6% series reactor mixed installation.
(3) The background harmonic at the access point of the capacitor device is the 5th order and above
1) The 5th harmonic content is small, and a series reactor of 4.5% to 6% should be selected.
2) The 5th harmonic content is relatively large, and a 4.5% series reactor should be selected.
3) For series reactors using 0.1% to 1%, it is necessary to prevent serious amplification or resonance of the 5th and 7th harmonics; for series reactors using 4.5% to 6%, it is necessary to prevent the 3rd harmonic. Severe amplification or resonance.